CVE-2026-11826OpenPLC_v3 Heap-Based Buffer Overflow in Modbus Master getData()
Updated under an hour ago ()
Does this affect you?
It affects openplcproject OpenPLC_v3. Add what you run to find out whether that includes you.
No exploitation reported and no EPSS estimate yet.
Do this next
Free account, 1 product
OpenPLC_v3 contains a heap-based buffer overflow in the getData() function in webserver/core/modbus_master.cpp. getData() reads characters between two delimiters into a caller-supplied buffer with no size parameter and no bounds check. In parseConfig() the function is invoked with the 100-byte heap-allocated MB_device.dev_name field. An authenticated attacker with access to the OpenPLC web interface can send a crafted HTTP POST to the /modbus endpoint with an oversized device_name value; the value is persisted to mbconfig.cfg and parsed on load, overflowing dev_name and overwriting adjacent struct fields (protocol at offset 108, dev_address at offset 109, ip_port at offset 210). A 200-byte payload writes 100 bytes past the allocation. The result is heap corruption leading to runtime crash and denial of service of the PLC process control loop, with attacker-controlled overwrite of adjacent configuration fields. The upstream repository was archived on 2026-04-04 and no fix is expected; the vendor has confirmed the issue does not affect OpenPLC Runtime v4.
- CVSS
- 8.8 HIGH (v3.1, CNA)CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H
- Weakness (CWE)
- CWE-122
- Known exploited
- Not in CISA's KEV catalog
- EPSS (exploitation in the next 30 days)
- Not loaded for this CVE
- Assigned by
- VulnCheck
- NVD analysis
- Deferred
- Record last updated
- Jul 27, 2026
- First seen by InfoSec Signals
- Oct 9, 2026
The CVE record on cve.org NVD's entry